Model |
SC-35-12 |
SC-35-24 |
|||
Output |
DC voltage |
CH1:13.8V |
CH1:13.4V |
CH1:27.6V |
CH2:26.5V |
|
Voltage tolerance |
±2% |
----- |
±1% |
----- |
|
Rated current |
2.0A |
0.5A |
1.0A |
0.3A |
|
Current range |
0~2.0A |
----- |
0~1.0A |
----- |
|
Rated power |
34.3W |
35.6W |
||
|
Ripple&noise |
120mvp-p |
----- |
120mvp-p |
----- |
|
DCvoltage ADJ.range |
CH1:11.3~14.9V |
CH1:21.3~29.8V |
||
|
Setup,rise,hold time |
800ms,50ms,80ms/230VAC, 1600ms,50ms,16ms/115VAC |
|||
|
Voltage range |
90~264VAC,127~370VDC |
|||
|
frequency |
47~63HZ |
|||
Input |
AC current |
0.9A/115VAC,0.45A/230VAC |
|||
|
efficiency |
81% |
83% |
||
|
Inrush current |
Cold start current 25A/115VAC,45A/230VAC |
|||
|
Leakage current |
< 1mA/240VAC |
|||
Protection |
Over load |
Rated output power110%~150% start over load protection |
|||
|
|
Protection mode: AC charging mode:hiccup mode auto-recovery after fault Condition is removed |
|||
|
Battery protection |
9.5~11V |
20~22V |
||
|
At low voltage |
Protection mode: cut off The output |
|||
Function |
UPS introduction |
Long-term online floating charge to battery, high charging efficiency, battery can saturate to more than 90% , cauto-stop harging when it's full, prevent over charging. Effectively extend battery life, AC/battery auto switch, no switch time, no need human guard, cold-start, when there is no AC input ,can use battery start UPS, Meet the user's emergency needs |
|||
Environment |
Working temp,humidity |
-10°C~+60°C,20%~90%RH |
|||
|
Storagetemp,humidity |
-20°C~+85°C,10%~95%RH non-condensing |
|||
|
Withstand vibration |
10~500HZ,2G 10min/1cycle,period for 60 minutes,each axes |
|||
Safety |
Withstand voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
|||
|
Isolated resistance |
I/P-O/P,I/P-FG,O/P-FG:100Mohms/500VDC |
|||
Others |
Dimension |
111*78*36mm (L*W*H) |
|||
|
Weight/packing |
43*34*24cm/45pcs/13.5kg |
|||
Note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and25°Cof ambient temperature. |
||||
|
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. |
||||
|
3. Tolerance : includes set up tolerance, line regulation and load regulation. |